4-20 mA Scaling Calculator

Convert current and voltage signals to measured values, find the PLC raw value and copy the ready-to-use SCL code.

Sensor measuring range
What do you want to enter?

Measured value

5

Signal

12 mA

PLC raw value

13,824

Share of measuring range

50 %

The value is within the valid measuring range.

Scaling in SCL (Siemens S7-1200 / S7-1500)

// raw 0 ... 27648  ->  0.0 ... 10.0
#value := SCALE_X(MIN := 0.0,
                  VALUE := NORM_X(MIN := 0, VALUE := #raw, MAX := 27648),
                  MAX := 10.0);

This is a purely mathematical calculation. Always rely on the datasheets of your sensor and analog module and on your controller configuration. No warranty.

How 4-20 mA scaling works

A sensor with a 4-20 mA output maps its measuring range linearly to the current: 4 mA is the start of the range and 20 mA is the end. The formula is: value = range start + (I − 4 mA) ÷ 16 mA × (range end − range start).

Example: a 0 … 10 bar pressure sensor at 12 mA gives (12 − 4) ÷ 16 × 10 = 5 bar.

Common values at a glance

SignalShare of measuring rangeRaw value
Siemens S70 … 27648INT160 … 32767UINT160 … 6553512 bit0 … 4095
4 mA0 %0000
8 mA25 %69128192163841024
12 mA50 %1382416384327682048
16 mA75 %2073624575491513071
20 mA100 %2764832767655354095

Frequently asked questions

Why does the signal start at 4 mA instead of 0 mA?

This "live zero" lets you tell a wire break or sensor failure (0 mA) apart from a valid start of range (4 mA). It also allows two-wire sensors to draw their power from the same current loop.

What does the raw value 27648 mean?

Siemens S7-1200, S7-1500 and ET 200 analog inputs deliver values from 0 to 27648 in the nominal range. Above that, depending on the module, there is an overrange area up to a maximum of 32511. The exact behaviour is described in the manual of your analog module.

Which raw value range should I choose?

It depends on your analog module. Siemens S7-1200, S7-1500 and ET 200 use 0 … 27648. Other controllers and modules often deliver the full positive range of a 16-bit value (INT16: 0 … 32767, UINT16: 0 … 65535), and simple 12-bit converters deliver 0 … 4095. Pick the matching range or enter your own raw values. The datasheet of your module is authoritative.

How do I detect a wire break?

If the current falls below 3.6 mA, NAMUR NE 43 treats it as a failure. Many analog modules report this as a "wire break" diagnostic. Evaluate that diagnostic in your program instead of relying on the scaled value alone.